Manufacturer |
---|
Star-delta timing relay IP41 PT420-8 POWER ELECTRONICS
It is used in automation devices for starting high power motors, ensuring a smooth transition from star to delta connection.
In addition to the basic star-delta delay time, an intermediate gap transition time can be set to avoid magnetic coupling of the two relays which leads to their simultaneous arming momentarily
Voltage (V): 230
Application: Starting three-phase motors in automation devices
Function: Starting motors via star-delta connection
Output relay: 2 independent, one switching contact 10A/250V cat. AC1
Delay time (delay): 3-30 sec
Transition time: 20-300 msec
Protection: Varistor (from surges & lightning)
Degree of Protection (IP): 41
Operating temperature: -20..+50 °C
LED indicators: Power ON & Relay ON
Connection base: Lamp type, 8P or 11P
Dimensions (mm): 42 x 89 x 94
44.79€